EN 60332-3-24 NHXH Safety Cable - FE180/E90 Fire Rating

0.6/1kV Fire Resistant Cable | 180-Min Fire Protection | 90-Min Circuit Integrity

$2.00

APPLICATION

Safety cables are used in all locations where a high degree of protection against fire and fire-damage has to be provided for human life and equipment and are, therefore, subject to high   security requirements. These cables may be used indoors.

They may not be installed directly into the ground or into water. Fire resistant to FE 180 and Circuit Integrity to E 90.

CHARACTERISTICS

Voltage Rating Uo/U

0.6/1kV

Temperature Rating

-5°C to +90°C

Minimum Bending Radius

RE: 12 x overall diameter

RM: 15 x overall diameter

CONSTRUCTION

Conductor

RE: Class 1 solid copper conductor

RM: Class 2 stranded copper conductor

Insulation

Flame protecting wrapping, LSZH (Low Smoke Zero Halogen)

Inner Sheath

LSZH (Low Smoke Zero Halogen)

Outer Sheath

LSZH (Low Smoke Zero Halogen)

Core Identification

3 cores: Brown  Blue  Green/Yellow

4 cores: Brown  Black Grey  Green/Yellow

5 cores: Brown  Black Grey  Blue Green/Yellow

7 core and above:  Black with White numbers

Sheath Colour

 Orange

STANDARDS

DIN VDE 0266, DIN VDE 0276-604, DIN VDE 0472 - 814, DIN 4102-12, EN 60228