FG7OH1M1/FG7OH2M1
Cable



Application and Description
These cables are suitable for environments with high fire hazards risk, where it’s essential to guarantee the safety of people and preserve systems and equipments from the corrosive gases (e.g. schools, hospitals, public premises, hotels, supermarkets, tubes, cinemas, theatres, discotheques, public offices). For fixed installation, both indoor and outdoor, on walls and metallic frames.
Standard and Approval
CEI 20-13
CEI 20-11
CEI 20-22 III
CEI 20-35 (EN60332-1)
CEI 20-37 pt.2 (EN50267)
Cable Construction
Flexible bare copper conductor to CEI 20-29 cl.5
Rubber HEPR, G7 quality,acc. to CEI 20-11
Not fibrous and not hygroscopic filler
Bare copper tape screen(for FG7OH1M1)
Bare copper wire braid(for FG7OH2M1)
Grey LSOH,type M1 outer jacket
Technical Characteristics
Working voltage | 600/1000 V |
Test voltage | 4000 V |
Minimum bending radius | 8 x Ø |
Flexing temperature | 0°C to +90°C |
Static temperature | -25°C to +90°C |
Maximum short circuit temperature | +250°C |
Flame retardant | CEI 20-22 III - IEC 60332-3-24 |
Insulation resistance | 10 MΩ x km |