H05VV5-F(NYSLYÖ-JZ)
Cable



Application and Description
These cables are suitable for dry, damp and wet locations but not in the open-air. They are used as screened termination and connection cable in the control, measuring and signal technology. The copper braiding optimises protection against external interferences, like electromagnetic fields and stray frequencies. Suitable as a signal and impulse cable for control and inspection of industrial plants, machinery and working processes.
Standard and Approval
CEI 20-20/13
CEI 20-35 (EN60332-1)
CEI 20-52
HD 21.13 S1
Cable Construction
Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5
PVC insulation TI2 to DIN VDE 0281 part 1
Green-yellow grounding (3 conductors and above)
Cores to VDE-0293 colors
PVC sheath TM5 to DIN VDE 0281 part 1
Technical Characteristics
Working voltage | 300/500v |
Test voltage | 2000volts |
2000voltsFlexing bending radius | 7.5 × Ø |
Static bending radius | 4 × Ø |
Flexing temperature | -5°C to +70°C |
Static temperature | -40°C to +70°C |
Short circuit Temperature | +150°C |
Flame retardant | IEC 60332.1 |
Insulation resistance | 20 MΩ × km |