LXV

Cable

Application and Description

These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, underground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Standard and Approval

IEC 60502-1 NP2365

Cable Construction

Aluminium conductor, class 1/class 2 to NP2363

XLPE insulation

Colour coded to HD 308

Not fibrous and not hygroscopic filler

Flexible PVC, type ST2 outer jacket

Technical Characteristics

Voltage Rating

600/1000V

Test voltage

3500 volts

Minimum bending radius

12 x Ø

Operation temperature range

-15°C to 90°C

Short-circuit temperature

250°C

Flame retardant

IEC 60332.1

Insulation resistance

1000 MΩ x km