N07V-K
Cable
Application and Description
These cables are suitable in building trade, industry, handicraft, wiring and power transport. Fitted inside pipes or ducts, either visible or recessed or similar closed systems. Suitable for static, protected use inside switching or control equipment, for alternating current up to 1000 V or direct current up to 750 V to ground. 1 mm² section is suitable only for circuits of lifting devices and machines. In fire risk installation the max operating temperature must not be above 55°C. Unsuitable for laying in the external and underground.
Standard and Approval
HD 21
CEI 20-22
CEI-UNEL 35752
CEI 20-52
IEC 332-3
Directive Low Voltage Directive 73/23/EEC and 93/68/EEC
ROHS compliant
Cable Construction
Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5
Special PVC R2 core insulation
Technical Characteristics
Working voltage | 450/750 v |
Test voltage | 2500 volts |
Minimum bending radius | 4.0 x O |
Maximum operating temperature | -10°C to +70o C |
Maximum short circuit temperature | +160o C |
Flame retardant | IEC 60332.1; CEI EN 50265-2-1; CEI 20-22 II |
Insulation resistance | 20 MΩ x km |