N2XBH Copper Conductor XLPE/HFFR Armoured Power Cable 0.6/1kV
Halogen-free flame-retardant armoured cable for safe power distribution in high-risk fire environments such as tunnels, hospitals, and data centers
$15.00


APPLICATION
The N2XBH cable can be used in refineries, hotels, schools,tunnels, high constructions, hospitals, power plants, data processing centers, populated business centers where there is a risk of fire.
CHARACTERISTICS
Voltage Rating Uo/U
0.6/1kV
Test Voltage
3.5kV
Temperature Rating
Maximum Operating: +90ºC
Maximum Short-Circuit: +250°C
Minimum Bending Radius
12 x overall diameter
CONSTRUCTION
Conductor
Class 2 Stranded copper
Insulation
XLPE (Cross-Linked Polyethylene)
Filler
HFFR (Halogen free flame retardant)
Armour
Double galvanized steel tape
Outer Sheath
HFFR (Halogen free flame retardant)
Core Identification
2 core: Blue Brown
3 core: ● Brown ● Black ● Grey
4 core: ●Blue ● Brown ● Black ● Grey
5 core: Blue ● Brown ● Black ● Grey ● Black
Sheath Colour
● Black ● Green
STANDARDS
DIN VDE 0276-604, TS HD 604.S1, IS 1516.1, IEC 60502-1