RHVMV

Cable

Application and Description

This 3 conductor cable can be used for indoor and outdoor applications consists of three phases, usually used in power networks, it also can be Installed in conduit and direct burial.

Standards

IEC 60502

IEC 60332-3-24(C)

Cable Construction

Compacted copper strands conductor

Stands to IEC 60228 Class 2

Semi-conducting conductor screen

XLPE insulation according to IEC 60502

Semi-conducting insulation screen

Individual copper wire and tape screen

PP fiber and PP tape filling

Binder tape

Extruded continuous PVC bedding type ST2 of standard IEC 60502

Galvanized steel wire armour

Flexible special PVC compound outer sheath type ST2 of standard IEC 60502

Technical Characteristics

Working voltage

6/10 KV

Test voltage

75 KV

Minimum bending radius

10 x Ø(fixed installation); 15x Ø(during operation)

Working temperature

-10°C to +90°C

Short circuit temperature

+250ºC

Flame retardant

IEC 60332.3

Insulation resistance

20 MΩ x km