RHVMV
Cable
Application and Description
This 3 conductor cable can be used for indoor and outdoor applications consists of three phases, usually used in power networks, it also can be Installed in conduit and direct burial.
Standards
IEC 60502
IEC 60332-3-24(C)
Cable Construction
Compacted copper strands conductor
Stands to IEC 60228 Class 2
Semi-conducting conductor screen
XLPE insulation according to IEC 60502
Semi-conducting insulation screen
Individual copper wire and tape screen
PP fiber and PP tape filling
Binder tape
Extruded continuous PVC bedding type ST2 of standard IEC 60502
Galvanized steel wire armour
Flexible special PVC compound outer sheath type ST2 of standard IEC 60502
Technical Characteristics
Working voltage | 6/10 KV |
Test voltage | 75 KV |
Minimum bending radius | 10 x Ø(fixed installation); 15x Ø(during operation) |
Working temperature | -10°C to +90°C |
Short circuit temperature | +250ºC |
Flame retardant | IEC 60332.3 |
Insulation resistance | 20 MΩ x km |
How to Reach Us