Halogen-Free Fire-Resistant Communication and Control Cable 150/250V

Screened safety cable for alarms, emergency lighting, and telecommunication systems with low smoke emission and flame-retardant design.

$8.00

Application:

Halogen-free special cables for interconnecting station equipment, telephone and teletransmission equipment and data transmission devices by means of analogue   and digital signals in control and signalling fire protections systems. The cables are used primarily as transmission and power suplly lines for line equipment (sensors,   linear modules) in supervised lines of fire signalling systems and autonomous fir extinguisher and smoke removal control systems. The cables are incorporated in systems used at the „0" moment of fire origination (the moment of fire detection by the central detector). The cables can be used for transmitting trigger signals or conditions to auxiliary devices, which are activated by the central fire signalling mechanism upon detection of a fire (e.g. disconnection of a residential ventilation system, downward movement of passenger lifts, switching off of the power supply of building). Static screen protects the cable against interferences of external magnetic fields.The cables are CPR classification acc. to EN 50575.

Technical data:

Thermal parameters:

Temperature range:

fixed installation: -40 °C to 80 °C

min. instalation temp.: -5 °C

max. installation temp: 50 °C

Electrical parameters:

Operating voltage: 150 V Test voltage:

AC: 1500 V

DC: 2250 V

Insulation resistance (min.): 200 MΩ x km Pair loop resistance at 20 °C (max.):

0,6 mm: 135,8 Ω/km

0,8 mm: 75 Ω/km

1,0 mm: 48 Ω/km

Mutual capacitance of pair at 1 kHz

(maximum): 150 nF/km    Mechanical parameters:

Min. bending radius: 10 x Ø


Design:

Cores:                               solid copper conductor class 1, acc. to EN 60228

Insulation:                        halogen-free compound

Core colors:                     acc. to table „conductor insulation colour” in Technical Data chapter (acc. to PN-T-90321:1992) 

Core arrangement:          cores twisted in pairs

Wrapping:                         polyester tape

Screen:                             aluminium backed polyester type with tinned copper drain wire 0,4 mm diameter

Outer sheath:                   halogen-free polymer compound; colour: red